FIRE MARSHAL BULLETIN
Acceptable Thread Standard for Fire Hose Couplings, Fittings,Hydrants, Fire Department Connections and Hose Connections on Standpipes
Please click here for the Fire Marshal Bulletin about thread standards.
FIRE MARSHAL BULLETIN 2025-003
May 26, 2025
Acceptable Thread Standard for Fire Hose Couplings, Fittings,
Hydrants, Fire Department Connections and Hose Connections on
Standpipes
Purpose
This document clarifies the position of the Calgary Fire Department (CFD) with respect to
acceptable threads on 38 mm and 65 mm couplings and fittings for use with firefighting hose
and hydrants, fire department connections and hose connections on standpipes. “Fittings” may
include but are not limited to hose valves with integrated threads, adapters, reducers, and
appliances. In coordination with provincial regulations, CFD’s standard for 65 mm couplings and
fittings is “Alberta Mutual Aid Thread” (AMA).
Background
CFD has become aware of the sale, purchase and install of couplings, fittings, hydrants, fire
department connections and hose connections on standpipes that do not comply with
longstanding provincially mandated thread specifications.
Alberta established the Alberta Mutual Aid Thread Regulation in 1958, covering 65mm (2 ½
inch) fire hose couplings and fittings. The regulation remained in force, with minor modifications,
to accommodate metric measurement and new lightweight materials, until 1986 when the
regulation was rescinded, and the specifications were codified in the Albert Fire Code. Alberta
Mutual Aid Thread" is the only approved specification for 65mm couplings and connections.
Furthermore, the National Fire Code Alberta Edition (NFC(AE)) directly addresses the
specifications under 2.2.6.1. in Division C.
Couplings, fittings and/or adapters that are advertised as being “compatible with” or
“equivalent to” this standard, but do not comply with the requirements are not
acceptable. It has become apparent that over the years components with British Columbia
Standard Threads (BCST) have been used in place of components machined to Alberta Mutual
Aid thread specification, impacting hose couplings, appliances, Fire Department Connections
and standpipe connections.
One of the primary challenges in connecting threads of different diameters lies in ensuring
proper engagement; as the difference in diameters increases, the contact face and the
thickness of the engaged material decrease exponentially, which is supported by a review of the
tolerances for both the AMA and BCST threads. If the AMA threaded component and the BCST
1threaded component is at the lower end of the tolerances there is a high probability of failure
under pressure, potentially affecting performance and safety.
Figure 1 AMA/BCST Thread Comparison
In order to address the concerns of the Calgary Fire Department 65mm hose couplings must
comply with the National Fire Code (AE) 2.2.6.1.(2).(b) and all specifications must meet those
outlined for the Alberta Mutual Aid Thread specifications.
• Buildings that are currently under construction must replace all BCST with AMA
threaded components prior to, or during the early, stages of construction.
• Owners of buildings constructed within the last Five (5) years may wish to reach out to
the responsible engineer to determine best course of action to comply with the National
Fire Code (AE).
• Owners for buildings greater than Five (5) years must provide a strategy to the fire
department on how they plan to ensure all threaded firefighting components will be
brought into compliance with the Albert Mutual Aid Thread specifications.
One option may be to use threaded adapters that are firmly secured or lockable (set screw or
similar) to convert BCST or other non-AMA threads to AMA threaded components or Female
swivel replacement. The BAT coupling was introduced 10–12 years ago and was presented as
a way of integrating BCST threaded components with AMA threaded couplings. BAT is not a
designed or engineered thread combination and is a combination of two separate thread
specifications.
Current Code and Legislative References
Article 2.2.6.1, Division C, National Fire Code – 2023 Alberta Edition
From Section 2.2.6.1: General Requirements for “Hose for Firefighting”
2.2.6.1. Hose for Firefighting
21) No person shall use, sell, offer for sale, purchase, lease or otherwise distribute 65 mm or 38
mm hose couplings or fittings intended for use on firefighting hose or fire hydrants by a
municipal fire department or fire crew, unless the couplings and fittings comply with this
Subsection. (See Note A-2.2.6.1.(1).)
2) Threaded firefighting hose couplings and fittings shall have threads that are
a) 38 mm straight iron pipe thread, also known as iron pipe thread (IPT) or National Pipe
Straight Hose (NPSH), on 38 mm couplings, or
b) Alberta Mutual Aid (AMA) thread, which has 3.15 threads per cm, with a major thread
diameter between 75.95 mm and 75.69 mm for male threads and 76.45 mm for female threads,
on 65 mm hose couplings and hydrant connections.
3) All firefighting hose couplings shall meet the requirements of CAN/ULC-S513, “Standard for
Threaded Couplings for 38 mm and 65 mm Fire Hose,” including Appendix A.
4) All firefighting hose with internal lug quick-connect couplings, commonlyreferred to as Storz
couplings, shall be in conformance with CAN/ULC-S543, “Standardfor Internal Lug Quick-
connect Couplings for Fire Hose.”
5) All firefighting hose shall be listed.
6) All firefighting hose shall be inspected, tested and maintained in accordance with NFPA
1962, “Standard for the Care, Use, Inspection, Service Testing, and Replacement of Fire Hose,
Couplings, Nozzles, and Fire Hose Appliances.”
Application to Pre-code Buildings
Article 2.1.1.1 of Division C of the National Fire Code – 2023 Alberta Edition speaks to the issue
of buildings or fire protection measures that do not conform to an applicable code (i.e., built prior
to the introduction of the first Alberta Building Code in April 1, 1974). In these cases, where no
approved guideline has been issued by the Provincial Fire Administrator, the building or fire
protection measure must be constructed or installed in a manner that provides a level of life
safety which is acceptable to the authority having jurisdiction.
As per Article 1.4.1.2 of Division A of the National Fire Code – 2023 Alberta Edition, the
authority having jurisdiction means a safety codes officer in the fire discipline exercising
authority pursuant to designation of powers and terms of employment in accordance with the
Safety Codes Act. Pre-code buildings that do not comply with the fire code currently in-force,
and with specific reference to the requirements discussed in this bulletin, will be dealt with on
a case-by-case basis by the AHJ.
Conclusion
To ensure the safety, compatibility, and regulatory compliance of firefighting infrastructure in
Calgary, it is essential that all 65mm hose couplings and related components adhere strictly to
the Alberta Mutual Aid (AMA) thread specifications, as mandated by the National Fire Code –
Alberta Edition. The continued use of British Columbia Standard Thread (BCST) components in
place of Alberta Mutual Aid (AMA) fittings pose a significant risk of equipment failure due to
mismatched thread profiles and tolerances. As such, immediate corrective action is required for
buildings under construction, and existing buildings must assess and implement strategies for
compliance. While a BCST/AMA adapter may serve as a transitional solution, they must be
clearly marked and verified as meeting AMA specifications.
3Failure to adhere to this legislatively mandated standard may adversely impact the timeliness of
fire department operations, the safety of firefighters, and increases the probability that standpipe
and/or sprinkler systems will not be available for use by emergency responders in a fire situation
which could lead to:
• The fire not being suppressed or controlled, which could lead to
• The spread of fire, which could lead to
• Harm to persons, and/or
• Damage to the building(s) or facility.
Additionally, persons who fail to adhere to this standard may be subject to actions pursuant to the
Safety Codes Act, RSA 2000.
Fire Safety Codes Officers may require that owners of properties equipped with non-
conforming fittings on private hydrants, fire department connections or hose
connections on standpipe systems replace the fitting(s).
Subject to Change
This bulletin is subject to any additional STANDATAs released by Alberta Municipal Affairs.
Questions regarding this document may be forwarded to FireLegal@calgary.ca
Glenn Baxter
Fire Marshal
Fire Inspections & Investigations